the monitor export file is attached
Dear Mr Miguel Thanks for the clues given but all are not working no 1- when i use Export the csv file is generated no2- base value for time normalization changed and tried but didnot work ( no plot found) no3 - longer simulation also tried but didnot work screen shot attached for opendss viewer Please guide on what can be done to remove bug OR some settings required? Regards P Mehta
Mr Davis, I have tried it by setting the property in the script. But still it is not working. Regards P Mehta
I am trying to view plot by selecting option of opendss viewer ( in the tab "set" , select> other option> opendssviewer > True ) , when I plot the monitor , opendss viewer is opened but chart is not plotted. when I selected opendssviewer= false , the monitor value is properly displayed on chart .Snapshot is attached for reference . Please guide how to draw chart using opendss viewer . Regards Pravin Mehta
Sorry for spelling error in the name, it may please be read as Roger
Thanks Mr Rogar It was modeled with 2 single phase 2 winding transformers ,as you said, it is working, Of course HV side phase 1 current is more than other two phases but OK that is expected from the construction of transformer and it is verified at site that the load flow ( currents ) results are same as the actual measured on panel. Thanks . Can you please share the model for a balancing transformer used for 2x25kV caternary systems. Regards, P Mehta
It is not V-V transformer but it has primary side delta and secondary V connection. ( Means primary side three terminals phase with delta connection ( V12=V23=V31=11.0 kV ,2400kVA and )secondary side one phase and other terminal grounded -open V connection ( v10=22.5kV ,2400KVA) It is traction transformer and this type of arrangement is done for balancing the traction load Regards, P. Mehta
Thanks Mr Roger, The hand sketch for the said transformer is attached herewith for your reference. Regards P Mehta