#1356 Fan efficacy for existing/altered systems

2022.3.0
Verified
None
Critical
Comp.Error
2022
Unaffected
CBECCr
2023-07-10
2023-06-08
Alea German
No

The mandatory requirements of Section 150.0(m)13 and 0.45 W/cfm are required for Entirely new or complete replacement space-conditioning systems (150.2(b)1C) and Entirely new or complete replacement duct systems (150.2(b)1D iia). Testing found that the Standard Design is set to the mandatory requirement of 0.45 W/cfm in various cases when it should not be, such as when only the ducts are altered. Set the Standard Design fan efficacy to 0.45 if the ducts are "new", otherwise set the Standard Design to the Proposed Design W/cfm.

The ACM does not specify how HVAC system fan efficacy should be treated. Consider adding.

Discussion

  • Scott Criswell

    Scott Criswell - 2023-07-06
    • status: New --> Fixed
     
  • Scott Criswell

    Scott Criswell - 2023-07-06

    ruleset fix checked into SVN @ r2380

    • added logic to maintain Proposed fan power for EAA runs where Fan or Ducts are not entirely 'New'
    • adjusted pre-analysis fan power too high error message logic to allow higher than mandatory fan powers in systems not 'New'
     
  • Ada Liu

    Ada Liu - 2023-07-06

    Frontier has tested and can confirm this is resolved.

     
  • Thao Chau

    Thao Chau - 2023-07-10
    • status: Fixed --> Verified