#1773 Thresholds for Temp sensors are not showing & state is wrong

3.2.1
closed-fixed
5
2014-12-16
2013-02-04
No

Thresolds for theTemperatures sensors are not showing up and also showing wrong state.

Thresholds needs to be enabled and updated to the Temp Sensors.
xml reply from the iLO contains threshold and currect status of the Temp sensors

Below XML Reply:

<TEMPERATURE>
<TEMP>
<LABEL VALUE = "Temp 1"/>
<LOCATION VALUE = "Ambient"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "26" UNIT="Celsius"/>
<CAUTION VALUE = "42" UNIT="Celsius"/>
<CRITICAL VALUE = "46" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 2"/>
<LOCATION VALUE = "CPU 1"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "40" UNIT="Celsius"/>
<CAUTION VALUE = "82" UNIT="Celsius"/>
<CRITICAL VALUE = "83" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 3"/>
<LOCATION VALUE = "CPU 2"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "40" UNIT="Celsius"/>
<CAUTION VALUE = "82" UNIT="Celsius"/>
<CRITICAL VALUE = "83" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 4"/>
<LOCATION VALUE = "Memory"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "31" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 5"/>
<LOCATION VALUE = "Memory"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "30" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 6"/>
<LOCATION VALUE = "Memory"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "30" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 7"/>
<LOCATION VALUE = "Memory"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "30" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 8"/>
<LOCATION VALUE = "Memory"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "31" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 9"/>
<LOCATION VALUE = "Memory"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "34" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 10"/>
<LOCATION VALUE = "Memory"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "39" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 11"/>
<LOCATION VALUE = "Memory"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "44" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 12"/>
<LOCATION VALUE = "I/O Board 7"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "43" UNIT="Celsius"/>
<CAUTION VALUE = "68" UNIT="Celsius"/>
<CRITICAL VALUE = "73" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 13"/>
<LOCATION VALUE = "I/O Board 6"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "42" UNIT="Celsius"/>
<CAUTION VALUE = "68" UNIT="Celsius"/>
<CRITICAL VALUE = "73" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 14"/>
<LOCATION VALUE = "I/O Board 5"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "41" UNIT="Celsius"/>
<CAUTION VALUE = "68" UNIT="Celsius"/>
<CRITICAL VALUE = "73" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 15"/>
<LOCATION VALUE = "I/O Board 4"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "39" UNIT="Celsius"/>
<CAUTION VALUE = "68" UNIT="Celsius"/>
<CRITICAL VALUE = "73" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 16"/>
<LOCATION VALUE = "I/O Board 3"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "37" UNIT="Celsius"/>
<CAUTION VALUE = "68" UNIT="Celsius"/>
<CRITICAL VALUE = "73" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 17"/>
<LOCATION VALUE = "I/O Board 2"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "35" UNIT="Celsius"/>
<CAUTION VALUE = "68" UNIT="Celsius"/>
<CRITICAL VALUE = "73" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 18"/>
<LOCATION VALUE = "I/O Board 1"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "34" UNIT="Celsius"/>
<CAUTION VALUE = "68" UNIT="Celsius"/>
<CRITICAL VALUE = "73" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 19"/>
<LOCATION VALUE = "CPU"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "28" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 20"/>
<LOCATION VALUE = "Memory"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "35" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 21"/>
<LOCATION VALUE = "Storage"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "26" UNIT="Celsius"/>
<CAUTION VALUE = "60" UNIT="Celsius"/>
<CRITICAL VALUE = "65" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 22"/>
<LOCATION VALUE = "System"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "60" UNIT="Celsius"/>
<CAUTION VALUE = "110" UNIT="Celsius"/>
<CRITICAL VALUE = "115" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 23"/>
<LOCATION VALUE = "System"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "43" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
<TEMP>
<LABEL VALUE = "Temp 24"/>
<LOCATION VALUE = "System"/>
<STATUS VALUE = "Ok"/>
<CURRENTREADING VALUE = "45" UNIT="Celsius"/>
<CAUTION VALUE = "87" UNIT="Celsius"/>
<CRITICAL VALUE = "92" UNIT="Celsius"/>
</TEMP>
</TEMPERATURE>

Discussion

  • Hemantha Beecherla

    hpitree output

     
  • Hemantha Beecherla

    Fixed in trunk revision 7530.

    Note:
    Sensor status will be handled with different fix.

     
  • Hemantha Beecherla

    • status: open --> closed-fixed
     
  • dr_mohan

    dr_mohan - 2013-06-20
    • Description has changed:

    Diff:

    --- old
    +++ new
    @@ -1,4 +1,3 @@
    -
     Thresolds for theTemperatures sensors are not showing up and also showing wrong state.
    
     Thresholds needs to be enabled and updated to the Temp Sensors.
    