Sir, Yes this simulator has both the reset process and test commands. Thanks once again for your valuable guidance. Regards, Nitish
Sir, I have used qtester and another master to test an RTU with GI interval 1 second. It works fine. Then i tried to simulate multiple disconnections by setting a router disconnect of 10 mins. after running this setup for sometime (around 17 hrs), RTU stopped responding to any I format ASDUs and only responds to U format and sends confirmation S format ASDUs. Any I format ASDU gets ignored by the RTU till the RTU is reinitialized locally and the end of initialization command is sent by the salve....
Sir, Thanks a lot! Your advice was extremely helpful. I can now simulate a fast GI interval using qtester on a low signal strength GSM/wifi network and check for link failures. Will provide an update when done. Regards Nitish
Sir, 1. Is it possible to change the GI_period which is default= 330 seconds to any other value in Qtester? How should one decide the GI interval time period? 2. i have come across a few implementations of IEC 104 where the master sends GI commands every second. The Second interrogation Activation is being sent by the master even while the slave is still sending I frames in response to a previous GI command. Is it really required to have such a fast GI interval when background scan and spontaneous...