What do you mean by VTS connected to the same port? How are the PCs connected to the network and how did you setup the port in VTS?
UUT_SKG did not specify a network.
You need to add two more parameters: BVLCI = ORIGINAL-UNICAST-NPDU DER = TRUE The VTS scripting documentation is outdated and incomplete. The Word document has examples that use DER but the VTS scripting html file does not. You need the BVLCI for VTS to pick up your DNET, DADR, and HOPCOUNT parameters. You need the DER to actually set that flag (otherwise it defaults to false/0). I'm a bit confused by your EXPECT. If IUT_ADDR points to the gateway, but your message's final destination is SIO_ADDR,...
As the error says, you're supposed to use an enumeration name. That's because the last-restart-reason is a property of type BACnetRestartReason. It sounds like the other test tools are a bit more forgiving. You should be using: last-restart-reason: detected-power-lost
Who-Has Script Error in tests 1d and 1f