Snap7 Communication problem with new version of LOGO!8
32/64 bit multi-platform Ethernet S7 PLC communication suite
Brought to you by:
davenardella
Good Morning
We have problem since new version of Siemens LOGO!8 PLC.
Until now, we have used PLC LOGO!8 (6ED1052-1MD08-0BA0) but Siemens have stop this PLC and replace by PLC LOGO!8 (6ED1052-1MD08-0BA1).
snap7.dll seems not be able to exchange with this new version.
How to solve it ?
Solved, it's was not snap7 problem, it was about new version of logo!8 and LogoSoft confort, now there is possibility to disable S7 protocol, and it'was disable by fault.