No Communication
Brought to you by:
zaphodikus
Looks like a great program but can't see my HMI. Connected through an ethernet switch through my ethernet adapter. Settings shows my computer name for local IP, nothing for Remote IP. I was assuming I could enter IP addresses manually since I also have a wireless adapter (tried disabling but didn't work either).
Thanks
The address you see is you computer's local IP, that is what must be entered into the HMI. Once the HMI tries to connect, the HMI's address will display top-left on the screen as an incomming connection. The simulator behaves pretty much like a normal PLC would. Let us know how it goes...