DPTtype in linknx 0.0.1.30 :
- 1.001 switching (on/off) (EIS1)
- 10.001 time (EIS3)
- 11.001 date (EIS4)
- 12.xxx 32bit unsigned integer (EIS11) / counter pulse : [0...4 294 967 295]
- 13.xxx 32bit signed integer / counter pulses : [-2 147 483 648 ... 2 147 483 647]
- 14.xxx 32 bit IEEE 754 floating point number higher values than for DPT 9.xxx can be transferred
- 16.000 "string (EIS15) to ASCII codes 0 to 127 / allow sending text of up to 14 characters
The coding of the individual characters corresponds to the datapoint types 4.001 and 4.002"
- 16.001 "string (EIS15) with range 0 to 255 / allow sending text of up to 14 characters
The coding of the individual characters corresponds to the datapoint types 4.001 and 4.002"
- 20.102 heating mode / HVACMode : [0...4]
- 28.001 variable length string object
- 29.xxx signed 64bit value
- 3.007 dimming (EIS2) (Relative dimming)
- 3.008 blinds
- 5.001 scaling (from 0 to 100%) / Absolute dimming / Scaling : % [0...100] Resol ~0.4%
- 5.003 angle (from 0 to 360deg) / Angle : ° [0...360] Resol ~1,4°
- 5.xxx 8bit unsigned integer (EIS6)
- 6.xxx 8bit signed integer (EIS14) / counter pulse : [-128...127]
- 7.xxx 16bit unsigned integer (EIS10) / pulse : [0...65 535]
- 8.xxx 16bit signed integer / pulse : [-32768...32768]
- 9.xxx 16 bit floating point number (EIS5)
New DPTtype after linknx 0.0.1.30 :
- 1.001 switching (on/off) (EIS1)
- 1.002 Bool
- 1.003 Enable
- 1.004 Ramp
- 1.005 Alarm
- 1.006 BinaryValue
- 1.007 Step
- 1.008 UpDown
- 1.009 OpenClose
- 1.010 Start
- 1.011 State
- 1.012 Invert
- 1.013 DimSendStyle
- 1.014 InputSource
- 10.001 time (EIS3)
- 11.001 date (EIS4)
- 12.xxx 32bit unsigned integer (EIS11) / counter pulse : [0...4 294 967 295]
- 13.xxx 32bit signed integer / counter pulses : [-2 147 483 648 ... 2 147 483 647]
- 14.xxx 32 bit IEEE 754 floating point number higher values than for DPT 9.xxx can be transferred
- 16.000 "string (EIS15) to ASCII codes 0 to 127 / allow sending text of up to 14 characters
The coding of the individual characters corresponds to the datapoint types 4.001 and 4.002"
- 16.001 "string (EIS15) with range 0 to 255 / allow sending text of up to 14 characters
The coding of the individual characters corresponds to the datapoint types 4.001 and 4.002"
- 2.001 Switch
- 2.002 Bool
- 2.003 Enable
- 2.004 Ramp
- 2.005 Alarm
- 2.006 BinaryValue
- 2.007 Step
- 2.008 Direction1_Control
- 2.009 Direction2_Control
- 2.010 Start
- 2.011 State
- 2.012 Invert
- 20.102 heating mode / HVACMode : [0...4]
- 232.600 RGBObject
- 28.001 variable length string object
- 29.xxx signed 64bit value
- 3.007 dimming (EIS2) (Relative dimming)
- 3.008 blinds
- 4.001 Char_ASCI
- 4.002 Char_8859_1
- 5.001 scaling (from 0 to 100%) / Absolute dimming / Scaling : % [0...100] Resol ~0.4%
- 5.003 angle (from 0 to 360deg) / Angle : ° [0...360] Resol ~1,4°
- 5.010 Value 1 pulse
- 5.xxx 8bit unsigned integer (EIS6)
- 6.xxx 8bit signed integer (EIS14) / counter pulse : [-128...127]
- 7.xxx 16bit unsigned integer (EIS10) / pulse : [0...65 535]
- 8.xxx 16bit signed integer / pulse : [-32768...32768]
- 9.001 Temp : °C
- 9.002 Tempd : °K
- 9.003 Tempa : K/H
- 9.004 Lux : lux
- 9.005 Wsp : m/s
- 9.006 Pres : Pa
- 9.007 Humidity : %
- 9.008 AirQuality : ppm
- 9.010 Time : s
- 9.011 Time : ms
- 9.020 Volt : mV
- 9.021 Current : mA
- 9.022 PowerDensity : W/m²
- 9.023 KelvinPerPercent : K/%
- 9.024 Power : kW
- 9.025 VolumeFlow : l/h
- 9.026 Rain_Amount : l/m²
- 9.027 Value_Temp_F : °F
- 9.028 Value_Wsp_kmh : km/h
- 9.xxx 16 bit floating point number (EIS5)