#1174 HRV ERV Remove or Change Default w/CFM

2019.1.3
Verified
None
Critical
Clarification
2019
TBD
CBECCr
2020-07-10
2019-12-02
No

The default is 0.25 w/CFM. In EDR it can make a huge difference. Either remove default and require actual or make it a more realistic "default". If 0.99 is actual we should not allow 0.25. This example file it makes 2.2 difference in Total EDR.

2 Attachments

Discussion

  • Diane Pepetone

    Diane Pepetone - 2020-02-11

    Just posted to SourceForge ResHvac schema changes with new properties for low/high rated fan flow capacity and SRE/ASRE values, and CF1R-PRF schema with new fields for section Ee IAQ Fans with this data.

     
  • RJ Wichert

    RJ Wichert - 2020-02-12

    New default should be equal to the Standard Design W/CFM (0.3 for Single Family or 0.6 for Multifamily)

    Dealing with old files with potentially default 0.25 W/CFM data:

    If file is from a version prior to 2019.2.0 and IAQ W/CFM = 0.25 : Blast IAQ W/CFM and require user to input new value.

     
  • Scott Criswell

    Scott Criswell - 2020-02-13
    • status: New --> Fixed
    • assigned_to: Bruce Wilcox --> Scott Criswell
     
  • Scott Criswell

    Scott Criswell - 2020-02-13

    Fix checked into SVN @ r1686 -
    LoadModelAdjustments rule to override old default IAQFan:WperCFMIAQ of 0.25 and replace w/ new 0.3-0.6 default (only for 2019.2.0+ releases)

     
  • Dee Anne Ross

    Dee Anne Ross - 2020-05-18
    • status: Fixed --> Verified